Effects of ambient temperature fluctuations

March 1, 2016

Ambient temperature fluctuations can affect differential pressure measurements.

A differential pressure transmitter with an upper range limit of 500 mbar and a set span of 0 to 250 mbar (approximately 0 to 100 inches) is installed outdoors. The transmitter has an ambient temperature effect specification of 0.001 percent upper range limit/°C plus 0.002 percent set span/°C. Approximately how is the flow accuracy of the transmitter affected by ambient temperature fluctuations of ±20°C?

A.    0.04 percent of flow rate
B.    0.08 percent of flow rate
C.    0.1 mbar
D.    0.2 mbar
E.    None of the above

Ambient temperature fluctuations can affect the differential pressure measurement by 0.01 • 0.001 • 500 plus 0.01 • 0.002 • 250, or 0.01 mbar/°C. This corresponds to a 0.2 mbar potential error for the ± 20°C temperature fluctuation. Answer D might appear to be correct, but it is an absolute (fixed) differential pressure error and not a flow error.

The 0.2 mbar potential error represents 0.08 percent of the set span of 250 mbar and would introduce approximately 0.04 percent of flow rate error when the flow is at 100 percent. The flow error at other flow rates will be different, so Answer A and Answer B are not correct.
Answer E is correct.

Additional complicating factors

Not only will the flow error be different at different flow rates, but the differential pressure transmitter can also be significantly affected by the static pressure at which it is measuring. In many applications, both temperature and pressure effects should be considered.

David W. Spitzer is a regular contributor to Flow Control magazine and a principal in Spitzer and Boyes LLC offering engineering; seminars; strategic marketing consulting; distribution consulting; and expert witness services for manufacturing and automation companies. Spitzer and Boyes is also the publisher of the Industrial Automation INSIDER. Spitzer has more than 40 years of experience and has written more than 10 books and 300 articles about flow measurement, instrumentation and process control. He may be reached at 845-623-1830 or at spitzerandboyes.com.

About the Author

David W. Spitzer

David W Spitzer’s new book Global Warming (aka Climate Change): An Understandable Data-Driven Explanation and Pathway to Mitigation (Amazon.com) adds to his over 500 technical articles and 10 books on flow measurement, instrumentation, process control and variable speed drives. David offers consulting services and keynote speeches, writes/edits white papers, presents seminars, and provides expert witness services at Spitzer and Boyes LLC (spitzerandboyes.com or +1.845.623.1830).

Sponsored Recommendations

Learn About: Micro Motion™ 4700 Config I/O Coriolis Transmitter

An Advanced Transmitter that Expands Connectivity

Micro Motion™ G-Series Compact, Drainable Coriolis Flow and Density Meters

Micro Motion G-Series Coriolis flow and density meters are ideally suited for Process Monitoring and Optimization applications, offering easy selection with pre-selected models...

Learn about: Micro Motion G-Series Coriolis Flow and Density Meters

The Micro Motion G-Series is designed to help you access the benefits of Coriolis technology even when available space is limited.

Micro Motion 4700 Coriolis Configurable Inputs and Outputs Transmitter

The Micro Motion 4700 Coriolis Transmitter offers a compact C1D1 (Zone 1) housing. Bluetooth and Smart Meter Verification are available.